  1. Micom S1 Software Download

MiCOM S1 Studio Software Request A link to download the MiCOM S1 studio software can be found by clicking Software/Firmware in the Downloads menu. Installation Guideline for Upgrading (Maintaining Installed Data Models).

P341/EN AD/F43 © 2011. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM. The other names
mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this document is provided for information only.
Micom s1 studio v 5.3.1
Neither ALSTOM, its officers or employees accept responsibility for, or should be taken as making any representation or warranty (whether express or implied), as to
the accuracy or completeness of such data or the achievement of any projected performance criteria where these are indicated. ALSTOM reserves the right to revise or
change this data at any time without further notice.
Update Documentation
Platform Hardware Version: J
Publication Reference:
GRID

Advertisement

Micom S1 Software Download

Also See for Micom P341

Related Manuals for Micom P341

Summary of Contents for Micom P341

  • Page 1 P341/EN AD/F43 P341/EN AD/F43 © 2011. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM. The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this document is provided for information only.
  • Page 3 Update Documentation P341/EN AD/F43 MiCOM P341 UPDATE DOCUMENTATION Date: February 2008 Hardware Suffix: Software Version: 10P341xx (xx = 01 to 04) Connection Diagrams:..
  • Page 4 P341/EN AD/F43 Update Documentation MiCOM P341..
  • Page 5 Update Documentation P341/EN AD/F43 MiCOM P341 (AD) -1 P341 UPDATE DOCUMENTATION Since versions 0300 & 0310J, several changes on existing features have been added. These are described with reference to the documentation listed below: Release Version Documentation 04.08.2006 P341/EN M/F33 Technical Manual Document Ref.
  • Page 6 P341/EN AD/F43 Update Documentation (AD) -2 MiCOM P341 Document Ref. Section Page No. Description P341/EN TD/F33 Protection functions Continued Overvoltage IDMT Pick-up: 1.05 x deleted Drop-off : 0.95 changed to 0.98 Measurements and recording facilities frequency : 5 changed to 40..
  • Page 7 What is IEC 61850? New section Interoperability 9.21 New section The data model New section 9.2.2 Figure 8 : new IEC 61850 in MiCOM relays New section Capability 9.3.1 New section IEC 61850 configuration 9.3.2 New section Configuration banks 9.3.2.1..
  • Page 8 MiCOM P341 Document Ref. Section Page No. Description P341/EN SC/F33 Network connectivity continued 9.3.2.2 New section The data model of MiCOM relays New section The communication services of MiCOM relays New section Peer-to-peer (GSE) communications New section Scope 9.6.1 New section IEC 61850 GOOSE configuration 9.6.2..
  • Page 9 Update Documentation P341/EN AD/F43 MiCOM P341 (AD) -1 TECHNICAL DATA (P341/EN TD/F33)
  • Page 10 EIA(RS)485 signal levels, two wire connections located on general purpose block, Design M4 screw. Modular MiCOM Px40 platform relay, P341 in For screened twisted pair cable, multidrop, 40TE case. Mounting is front of panel flush 1000m max. mounting, or 19“ rack mounted with rack frame For K-Bus, IEC-60870-5-103, MODBUS or (ordering options).
  • Page 11 Update Documentation P341/EN AD/F43 MiCOM P341 (AD) -7 AC Current Power Supply Interruption Nominal current (In): 1 and 5 A dual rated. Per IEC 60255-11: 1979: (1A and 5A inputs use different transformer tap The relay will withstand a 20ms interruption..
  • Page 12 P341/EN AD/F43 Update Documentation (AD) -8 MiCOM P341 Output Contacts Standard Contacts Environmental Conditions General purpose relay outputs for signaling, tripping and alarming: Ambient Temperature Range Rated voltage: 300 V Per IEC 60255-6: 1988: Continuous current: 10 A Operating temperature range: Short-duration current: 30 A for 3 s -25°C to +55°C (or -13°F to +131°F)
  • Page 13 Update Documentation P341/EN AD/F43 MiCOM P341 (AD) -9 Between all independent circuits. Immunity to Radiated Electromagnetic Between all independent circuits and Energy protective (earth) conductor terminal. Per IEC 60255-22-3: 2000, Class III: Test field strength, frequency band 80 to 1000 Between the terminals of independent circuits.
  • Page 14 P341/EN AD/F43 Update Documentation (AD) -10 MiCOM P341 EU Directives Mechanical Robustness EMC Compliance Vibration Test Per 2004/108/EC: Per IEC 60255-21-1: 1996: Compliance to the European Commission Response Class 2 Directive on EMC is claimed via the Technical Endurance Class 2 Construction File route.
  • Page 15 Update Documentation P341/EN AD/F43 MiCOM P341 (AD) -11 Sensitive/Low Forward/Over Power Thermal Overload Accuracy Accuracy Pick-up: Setting 10% Setting accuracy: 5% Reset: 95% of thermal setting 5% Reverse/Over power Drop-off: 0.9 of setting 10% Thermal alarm Pick-up: Calculated trip time 5% Low forward power Drop-off: 1.1 of Setting 10%..
  • Page 16 P341/EN AD/F43 Update Documentation (AD) -12 MiCOM P341 Negative Sequence Polarizing Quantities Reconnect Delay Accuracy Operating boundary Pick-up: 2 of RCA 90 Accuracy Hysteresis: <3 Operating time: 2% or 50ms whichever is V2pol Pick-up: Setting 10% greater V2pol Drop-off: 0.9 x Setting or 0.7V (whichever is greater) 10%..
  • Page 17 Update Documentation P341/EN AD/F43 MiCOM P341 (AD) -13 Programmable Scheme Logic Overfrequency Accuracy Accuracy Output conditioner timer: Setting 2% or 50ms Pick-up: Setting 0.01Hz whichever is greater Drop-off: (Setting -0.025Hz) 0.01Hz Dwell conditioner timer: Setting 2% or 50ms DT operation: 2% or 50ms whichever is..
  • Page 18 P341/EN AD/F43 Update Documentation (AD) -14 MiCOM P341 CLI sampling interval: 50ms Parameter Min. Typ. Max. Unit CLI instantaneous operating time: < 250ms Output Optical CLI DT operating time: 2% setting or 200ms Power BOL whichever is the greater 62.5/125 µm, -16.8..
  • Page 19 Update Documentation P341/EN AD/F43 MiCOM P341 (AD) -15 Opto+Rem+local CB Fail: Disabled/Enabled Close Pulse Time: 0.10..10.00s Supervision: Disabled/Enabled Trip Pulse Time: 0.10…5.00s Input Labels: Invisible/Visible Man Close t max: 0.01…9999.00s Output Labels: Invisible/Visible Man Close Delay: 0.01…600.00s CT & VT Ratios: Invisible/Visible CB Healthy Time: 0.01…9999.00s..
  • Page 20 P341/EN AD/F43 Update Documentation (AD) -16 MiCOM P341 Input 1 Trigger: No Trigger/Trigger/LH (Low to Optional Ethernet Port High)/Trigger H/L (High to Low) NIC Tunl Timeout: 1..30mins (up to): NIC Link Report: Alarm, Event, None Input 32 Trigger: No Trigger/Trigger NIC Link Timeout: 0.1..60s..
  • Page 21 Update Documentation P341/EN AD/F43 MiCOM P341 (AD) -17 Opto Coupled Binary Inputs Settings in Multiple Groups (Opto Config) Note: All settings here onwards apply for setting groups # = 1 to 4. Global Nominal V: 24 - 27V 30 - 34V..
  • Page 22 P341/EN AD/F43 Update Documentation (AD) -18 MiCOM P341   Phase Overcurrent (Overcurrent)   (/ s )  - 1 Phase O/C: Sub Heading t = TD x     I>1 Function: Disabled Where: IEC S Inverse..
  • Page 23 Update Documentation P341/EN AD/F43 MiCOM P341 (AD) -19 = Constant M = /s Curve Description Standard Moderately inverse IEEE 4.85 Very inverse IEEE 21.6 Extremely inverse IEEE 29.1 Inverse 5.95 Short time inverse 2.261 The RI curve (electromechanical) has been..
  • Page 24 P341/EN AD/F43 Update Documentation (AD) -20 MiCOM P341 Amercian Curves T-heating: 1…200 minutes T-cooling: 1…200 minutes M Factor: 0…10 The thermal time characteristic is given by: t =  loge (eq - P - (Thermal >) )/(eq t = . loge ((K..
  • Page 25 Update Documentation P341/EN AD/F43 MiCOM P341 (AD) -21 Non-Directional SEF/REF Prot’n Directional Fwd SEF/REF Options: Directional Rev IN1>3 Current Set: 0.08…32.00 In SEF Cos (PHI) IN1>3 Time Delay: 0.00…200.00s SEF Sin (PHI) IN1>4 as IN>3 Wattmetric IN1> Blocking: Hi Z REF Binary function link string, selecting which ISEF>1 Function:..
  • Page 26 P341/EN AD/F43 Update Documentation (AD) -22 MiCOM P341 V<2 Status: Disabled/Enabled Restricted Earth Fault V<2 Voltage Set: (High Impedance) 10…120V (100/120V) IREF> Is: 0.05.1.00 In 40…480V (380/480V) V<2 Time Delay: 0.00…100.00s Residual O/V NVD V<2 Poledead Inh: Disabled/Enabled VN>1 Status: Disabled/Enabled The inverse characteristic is given by the VN>1 Input: Derived..
  • Page 27 Update Documentation P341/EN AD/F43 MiCOM P341 (AD) -23 Current Transformer Supervision CTS 1 Status: Disabled/Enabled CTS 1 VN Input: Measured/Derived Frequency Protection CTS 1 VN< Inhibit: 0.5…22V (100/120V) 2…88V (380/480V) Underfrequency CTS 1 IN> Set: 0.08…4In F<1 Status: Disabled/Enabled F<1 Setting: 45.00…65.00 Hz F<1 Time Delay: 0.1…100.0s..
  • Page 28 P341/EN AD/F43 Update Documentation (AD) -24 MiCOM P341 CLI1 Minimum: -9999…+9999 V2 Magnitude CLI1 Maximum: -9999…+9999 V0 Magnitude CLI1 Alarm: Disabled/Enabled 0.0…200.0V CLI1 Alarm Fn: Over/Under RMS Phase Voltages: CLI1 Alarm Set: CLI1 min…CLI1 max VAN RMS* CLI1 Alarm Delay: 0.0…100.0s..
  • Page 29 Update Documentation P341/EN AD/F43 MiCOM P341 (AD) -25 3Ph Power Factor Ph Power Factor Independent power factor measurements for  Measurements List all three phases ( = A, B, C). 3Ph WHours Fwd 3Ph WHours Rev Measurements 1 3Ph VArHours Fwd I..
  • Page 30 Update Documentation (AD) -26 MiCOM P341 APPLICATION NOTES (P341/EN AP/F33) Configuration column The P34x relays include a column in the menu called the “CONFIGURATION” column. This affects the operation of each of the individual protection functions. The aim of this column is to allow general configuration of the relay from a single point in the menu.
  • Page 31 Update Documentation P341/EN AD/F43 MiCOM P341 (AD) -27 Menu Text Default Setting Available Settings Function Makes settings visible Power Enabled Enabled or Disabled in the relay menu Makes settings visible Thermal Overload Enabled Enabled or Disabled in the relay menu..
  • Page 32 2.3.1 Description A facility is provided in the P341 to maintain correct operation of all the protection functions even when the generator is running in a reverse phase sequence. This is achieved through user configurable settings available for the four setting groups.
  • Page 33 (Vbc, Vca, Vab) is reversed by the change in phase rotation. Note, CT2 is not applicable to P341/2 relays only P343/4/5 relays which include differential protection. The relationship between voltages and currents from CT1 for the standard phase rotation and reverse phase rotation are as shown below.
  • Page 34 P341/EN AD/F43 Update Documentation (AD) -30 MiCOM P341 The Phase Sequence setting applies to a power system that has a permanent phase sequence of either ABC or ACB. It is also applicable for temporary phase reversal which affects all the VTs and CTs. As distinct from the other phase reversal settings, this setting does not perform any internal phase swapping of the analogue channels.
  • Page 35 LED’s etc. The complete list of these signals may be found by viewing the available settings in the relay menu or via a setting file in MiCOM S1. Any of the digital channels may be selected to trigger the disturbance recorder on either a low to high or a..
  • Page 36 (e.g. relay 3) will trigger the recorder. It is not possible to view the disturbance records locally via the LCD; they must be extracted using suitable software such as MiCOM S1. This process is fully explained in SCADA Communications (P341/EN SC).
  • Page 37 Update Documentation P341/EN AD/F43 MiCOM P341 (AD) -33 In the default PSL, Relay 3 is still mapped to the “Any Trip” DDB and the “Fault REC TRIG” DDB signals. If the user wants to make use of the CB maintenance features, CB failure function etc.
  • Page 38 P341/EN AD/F43 Update Documentation (AD) -34 MiCOM P341 Setting Range Menu Text Default Setting Step Size Min. Max. LocalTime Enable Fixed Disabled/Fixed/ Flexible Setting to turn on/off local time adjustments. Disabled - No local time zone will be maintained. Time synchronization from any interface will be used to directly set the master clock and all displayed (or read) times on all interfaces will be based on the master clock with no adjustment.
  • Page 39 NIT/TIA often specified historically. The table below recommends advisory limits on relays connected per fused spur. This applies to MiCOM Px40 series devices with hardware suffix C and higher, as these have inrush current limitation on switch-on, to conserve the fuse-link.
  • Page 40 ALSTOM Grid Automation's offer of a full IEC 61850 solution for the substation. The majority of MiCOM Px3x and Px4x relay types can be supplied with Ethernet, in addition to traditional serial protocols. Relays which have already been delivered with UCA2.0 on Ethernet can be easily upgraded to IEC 61850.
  • Page 41 Update Documentation P341/EN AD/F43 MiCOM P341 (AD) -37 9.2.2 The data model To ease understanding, the data model of any IEC 61850 IED can be viewed as a hierarchy of information. The categories and naming of this information is standardized in the IEC 61850 specification.
  • Page 42 Logical Node type XCBR. IEC 61850 in MiCOM relays IEC 61850 is implemented in MiCOM relays by use of a separate Ethernet card. This card manages the majority of the IEC 61850 implementation and data transfer to avoid any impact on the performance of the protection.
  • Page 43 In order to keep this process as simple as possible, such setting changes are done using MiCOM S1 Settings & Records program. This can be done as previously using the front port serial connection of the relay, or now optionally over the Ethernet link if preferred (this is known as “tunneling”).
  • Page 44 The relay can be configured to accept data from networks other than the local network by using the ‘Gateway’ setting. The data model of MiCOM relays The data model naming adopted in the Px30 and Px40 relays has been standardized for consistency.
  • Page 45 32 virtual inputs within the PSL. The virtual inputs allow the mapping to internal logic functions for protection control, directly to output contacts or LEDs for monitoring. The MiCOM relay can subscribe to all GOOSE messages but only the following data types can be decoded and mapped to a virtual input: ..
  • Page 46 IEC 61850 GOOSE configuration All GOOSE configuration is performed via the IED Configurator tool available within the MiCOM S1 Support Software. All GOOSE publishing configuration can be found under the ‘GOOSE Publishing’ tab in the configuration editor window. All GOOSE subscription configuration can be found under the ‘External Binding’..
  • Page 47 Not used Not used Table 4: Signals on the Ethernet connector RELAY DESCRIPTION (P341/EN HW/F33) 1.1.6. Ethernet board This is a mandatory board for IEC 61850 enabled relays. It provides network connectivity through either copper or fiber media at rates of 10Mb/s (copper only) or 100Mb/s. There is also an option on this board to specify IRIG-B port (modulated or un-modulated).
  • Page 48 High break relay board One ‘high break’ output relay board consisting of four normally open output contacts is available for the P341 as an option. This board contains a hybrid of MOSFET solid state devices (SSD) in parallel with high capacity relay output contacts.
  • Page 49 In traditional hardwired scheme designs, high break capability could only be achieved using external electromechanical trip relays. External MVAJ tripping relays can be used or the new high break contacts inside MiCOM relays can be used – reducing panel space. 2) Accessibility of CB auxiliary contacts Common practice is to use circuit breaker 52a (CB Closed) auxiliary contacts to break the trip coil current on breaker opening, thus easing the duty on the protection contacts.
  • Page 50 MiCOM high break contacts will avoid the risk of burnt relay contacts. 4) Initiation of teleprotection The MiCOM high break contacts also offer fast making. This can provide faster tripping: additionally, fast keying of teleprotection is a benefit. Fast keying bypasses the usual contact operation time, such that permissive, blocking and intertrip commands can be routed faster.
  • Page 51 Update Documentation P341/EN AD/F43 MiCOM P341 (AD) -47 Figure 5: Ethernet board (optional) FIRMWARE AND SERVICE MANUAL VERSION HISTORY (P341/EN VH/F33)
  • Page 52 Relay type: P341 … Software Hardware Original Date Technical Version Description of Changes Suffix of Issue Compatibility Documentation Major Minor  Oct 1999 Original Issue V1.09 or Later TG8617A  Corrected degree phase angle displacement measurement of Ia, Ib, Ic Dec 1999 V1.09 or Later..
  • Page 53 Relay type: P341 … Software Hardware Original Date Technical Version Desc ription of Changes Suffix of Issue Compatibility Documentation Major Minor  Event filtering added  Jan 2001 Correction to energy measurement inaccuracy V2.00 or Later P341/EN T/B11  Minor bug fixes ..
  • Page 54 Relay type: P341 … Software Hardware Original Date Technical Version Description of Changes Suffix of Issue Compatibility Documentation Major Minor  Correction to undervoltage stage 2 (V<2) setting range. The setting range has been increased from 10-70V to 10-120V (Vn=110/120V) so that it is the same as V<1 ..
  • Page 55 Relay type: P341 … Software Hardware Original Date Technical Version Description of Changes Suffix of Issue Compatibility Documentation Major Minor  Correction to the fault recorder window for current based trips so that it can terminate properly once the FAULT_REC_TRIG signal (DDB 288) is reset.
  • Page 56 Relay type: P341 … Software Hardware Original Date Technical Version Description of Changes Suffix of Issue Compatibility Documentation Major Minor  For Courier/DNP 3.0/IEC60870-5-103 builds only.  Correction to parity setting for MODBUS and DNP 3.0 when the relay is powered up.
  • Page 57 Relay type: P341 … Software Hardware Original Date Technical Version Description of Changes Suffix of Issue Compatibility Documentation Major Minor  Not released to production  Sensitive reverse power added  Neutral voltage displacement threshold, VN>1/2, increased from 50 to 80V (Vn=100/120V), 200 to 320 V (Vn=380/480V) June 2001 V2.01 or Later..
  • Page 58 Relay type: P341 … Software Hardware Original Date Technical Version Description of Changes Suffix of Issue Compatibility Documentation Major Minor  Correction to MODBUS CB Trip and Close via '0' command  Change to neutral voltage displacement protection and directional SEF protection so that they are not blocked by the VT supervision logic when the VN Input and ISEF>VNPol are..
  • Page 59 Relay type: P341 … Software Hardware Original Date Technical Version Description of Changes Suffix of Issue Compatibility Documentation Major Minor  Correction to the fault recorder window for current based trips so that it can terminate properly once the FAULT_REC_TRIG signal (DDB 288) is reset.
  • Page 60 Relay type: P341 … Software Hardware Original Date Technical Version Description of Changes Suffix of Issue Compatibility Documentation Major Minor  For MODBUS builds only  Changes as for H  Improvement to the MODBUS driver to cope better with July 2004 V2.01 or Later..
  • Page 61 Relay type: P341 … Software Hardware Original Date Technical Version Description of Changes Suffix of Issue Compatibility Documentation Major Minor  Not released to production  Correction to VT ratio scaling problem in the disturbance recorder Oct 2001 V2.05 or Later P341/EN T/D22 ..
  • Page 62 Relay type: P341 … Software Hardware Original Date Technical Version Description of Changes Suffix of Issue Compatibility Documentation Major Minor  DNP 3.0 Object 12 “CROB” implementation is now compliant for simple function points  Correction to MODBUS CB Trip and Close via '0' command ..
  • Page 63 Relay type: P341 … Software Hardware Original Date Technical Version Description of Changes Suffix of Issue Compatibility Documentation Major Minor  Control input sales added to non volatile memory  German language text updated  Power measurement limits added to prevent non zero values..
  • Page 64 Icd  Correction to the C32CS error when extracting and saving an uncompressed disturbance record from the P341 through the front port using MiCOM S1. This only applies to P341 IEC60870-5-103 protocol builds since this is the only..
  • Page 65 Relay type: P341 … Software Hardware Original Date Technical Version Description of Changes Suffix of Issue Compatibility Documentation Major Minor  For Courier/DNP 3.0/IEC60870-5-103 builds only  Correction to parity setting for MODBUS and DNP 3.0 when the relay is powered up June 2004 V2.05 or Later..
  • Page 66 DNP  IEC60870-5-103. Status of summer bit now works correctly in time sync command.  Correction to DNP 3.0 software where settings download from MiCOM S1 can fail for relays that have model dependent I/O configurations.  Minor bug fixes..
  • Page 67 Relay type: P341 … Software Hardware Original Date Technical Version Description of Changes Suffix of Issue Compatibility Documentation Major Minor  Not released to production  Additional IDMT characteristics for overcurrent protection (rectifier and RI curve), earth fault protection (RI and IDG curve) and sensitive earth fault protection (IDG curve) ..
  • Page 68 Relay type: P341 … Software Hardware Original Date Technical Version Description of Changes Suffix of Issue Compatibility Documentation Major Minor  Maximum overfrequency protection setting increased from 65 to 68 Hz  Change to undervoltage stage 2 (V<2) setting range to correct an error.
  • Page 69 Relay type: P341 … Software Hardware Original Date Technical Version Description of Changes Suffix of Issue Compatibility Documentation Major Minor  For Courier/DNP 3.0/IEC60870-5-103 builds only.  Correction to parity setting for MODBUS and DNP 3.0 when the relay is powered up.
  • Page 70 Relay type: P341 … Software Hardware Original Date Technical Version Description of Changes Suffix of Issue Compatibility Documentation Major Minor  Not released to production  Optional additional 4 analogue inputs and 4 outputs (current loop inputs and outputs – CLIO) ..
  • Page 71 Relay type: P341 … Software Hardware Original Date Technical Version Description of Changes Suffix of Issue Compatibility Documentation Major Minor  Correction to the CB trip/Close functionality via MODBUS so that local/remote setting in the CB Control menu is not ignored ..
  • Page 72 Relay type: P341 … Software Hardware Original Date Technical Version Description of Changes Suffix of Issue Compatibility Documentation Major Minor  Resolved possible reboot caused by failure to time sync from DNP 3.0 when IRIG-B is active which is also providing the time sync.
  • Page 73 Relay type: P341 … Software Hardware Original Date Technical Version Description of Changes Suffix of Issue Compatibility Documentation Major Minor  For Courier/DNP 3.0/IEC60870-5-103 builds only  Correction to parity setting for MODBUS and DNP 3.0 when the relay is powered up June 2004 V2.09 or Later..
  • Page 74 Not released to production.  Enhanced main processor board  Company name change. 'ALSTOM' changed to 'MiCOM' in default Plant Reference cell and 'ALSTOM P' changed to 'MiCOM P' for ASDU5 message type, IEC protocol.  User interface enhancements - larger 100x33 pixel graphical display of 3 lines x 16 characters + 2 new buttons, direct access keys.
  • Page 75 Relay type: P341 … Software Hardware Original Date Technical Version Description of Changes Suffix of Issue Compatibility Documentation Major Minor  Uncompressed disturbance recording added Courier/MODBUS/DNP 3.0 (added to IEC60870-5-103 protocol in 05D, 06B software)  Dual Characteristic DO/PU ratio Opto Inputs (DO/PU = 60/80% or 50/70%) ..
  • Page 76 Correction to 2nd rear comms port channel failure for P34xxxxxxxxxxxJ relays only.  Independent derived/measured neutral voltage protection (59N). P341 has 2 stages of measured and 2 stages of derived neutral voltage protection. Previous software versions included 2 stages of measured or derived neutral voltage protection.
  • Page 77 In P34x relays the maximum number of disturbance recorder analogue channels has been increased in most relay models so that all analogue inputs can be recorded. In the P341 the maximum number of recorded channels has remained as 8 but now channels can be set as unused if required.
  • Page 78  Minor bug fixes  Correction to P341 Directional Sensitive Earth Fault (Forward or reverse) function. Function does not operate if SEF/REF Protection is initially disabled in the configuration column and SEF Mode is set to 'SEF' (default setting) when the relay is P341/EN M/E33, booted up.
  • Page 79 Support released for high break contacts and de-modulated IRIG-B P341/EN M/E33, Dec 2007 V2.14 or later in all P34x relays. P341 relays can be ordered with modulated or P341/EN AD/E43 de-modulated IRIG-B and with 4 high break contacts.  Minor bug fixes..
  • Page 80 Relay Software Version                                      ..
  • Page 81 Relay Software Version                                      ..
  • Page 82 Relay Software Version                                      ..
  • Page 83 Update Documentation P341/EN AD/F43 MiCOM P341 (AD) -79 ORDERING INFORMATION P341 Generator Protection Relay P341 Vx Aux Rating 24-48 Vdc 48-110 Vdc, 30-100 Vac 110-250 Vdc, 100-240 Vac I/n/Vn Rating In=1A/5A, Vn=100/120V In=1A/5A, Vn=380/480V Hardware Options Nothing IRIG-B only (Modulated) Fiber Optic Rear Comms Port IRIG-B (Modulated) &..
  • Page 84 P341/EN AD/F43 Update Documentation (AD) -80 MiCOM P341 Design Suffix Original hardware Universal optos, new relays, power supply Phase 2 CPU Note Design Suffix A = Original hardware (48V opto inputs only, lower contact rating, no I/O expansion available) C = Universal optos, new high capacity relays, new power supply..
  • Page 86 PXXX Product Description Alstom Grid © - ALSTOM 2011. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM. The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this document is provided for information only.
Contact Us
Engineering Tool Suite

Discover the next generation in tools for configuration and maintenance of MiCOM – redefining MiCOM S1. S1 Agile is the next step enhancement from existing MiCOM S1 Studio, encompassing all of the traditional functionality, to become the complete successor. The move from S1 Studio to S1 Agile underlines Alstom’s R&D investment in usability: to assemble all tools in a palette for simple entry, with intuitive navigation via fewer mouse-clicks.

S1 Agile is the truly universal PC tool for MiCOM for the first time. No-longer are separate tools required for redundant Ethernet configuration, phasor measurement unit commissioning, busbar scheme operational dashboards, programmable curve profiles or automatic disturbance record extraction – all applications are embedded. MiCOM S1 Agile supports all existing MiCOM, K-Series and Modulex, including a utility for automatic conversion of setting files from previous generations of numerical relays like K-series and MiCOM P20 to the latest P40 Agile models.

To move to the future, with no loss of functionality, no loss of device support, and full compatibility with your installed base and system architecture – request a copy of S1 Agile with the contact form link below.

Key features in the MiCOM S1 family:

  • GE’s integrated engineering tool that provides users with access to all automation IED configuration and record data
  • Integrated configuration and monitoring features
  • Send and extract setting files
  • Event and disturbance record extraction and analysis
  • S1 Agile only: Integrated programmable curve tool and RSTP redundant Ethernet configuration for protection relays
  • S1 Agile only: Integrated automatic extraction of disturbance records facility
  • S1 Agile only: Integrated P740 and P746 remote HMI and topology tools for busbar schemes

Key benefits:

  • Powerful, free of charge, PC toolsuite
  • Optimum management of the installed base, structured as per the substation topology
  • Intuitive and versatile interface with file management facilities
  • Logical structure based on substation, voltage level and bay
  • Version control and cross-checking facilities for IED settings
  • Real-time measurement visualization - S1 Agile extends to all IEDs - including P847 PMU and busbar schemes
  • S1 Agile only: Convert K-series and P20 series settings files to MiCOM P40 Agile relay equivalents - the future for distribution and industry protection
  • S1 Agile only: Select the latest substation IEDs from the extensive MiCOM Alstom, MiCOM P40 Agile and MiDOS ranges

S1 Agile offers a fresh new look - functions and components are presented as “tiles” rather than menu items.

S1 software request

To receive the S1 Agile, or any other MiCOM PC tools software by download, please use our Contact form. This will also ensure that you are kept up-to-date with all the latest enhancements, including updates and bug fixes.

Brochure in EnglishBrochure in PolishTechnical Manual Manual pdf download.